UPS on-line double conversion (DeltaAmplon RT 2kVA) 2kVA 1ph
Valid Article
UPS on-line double conversion (DeltaAmplon RT 2kVA) 2kVA 1ph
Definition
A double conversion uninterruptible power supply (UPS) guarantees a perfect AC supply and is especially suitable for vulnerable and/or expensive equipment such as medical and laboratory equipment.
There is no connection between the incoming power and the outgoing power; all possible electrical problems such as voltage spikes are eliminated.
To function in the case of a power-cut it needs a battery pack, which has to be ordered separately.
Specifications
- Input voltage range 175 - 280 V (note that between 175 V and 180 V input voltage, the output power is reduced by 50 - 100%; full power is available only at 180V AC and above). At higher (>300 V) or lower (<100 V) voltages the UPS switches to battery power
- Input and output frequency 50 or 60 Hz
- Power factor >0.99
- Efficiency (full load) >92%
- Battery cabinet: 4 x 9 Ah, 12 V batteries in one cabinet; energy content approximately 400 Wh.
- Multiple outputs allow for support of only critical loads.
Instructions for use
This UPS is primarily intended to protect the equipment connected to it. It also provides back-up power but it is limited with only one battery pack. Additional battery pack can be added to give a longer back-up time but the charger is integral and cannot be changed.
The output power makes it suitable for almost any laboratory or medical facility. The UPS is delivered without a power cord and needs to be wired with an appropriate cable. For more details and advice: contact your logistics department.
MSF requirements
The chosen model enables input voltages of 100 – 300 V to be converted to 230 V; the input is compatible with 50 or 60 Hz; the output can be programmed to the local frequency if need be.