LIGHTNING-SURGE PROT. type2 (Dehn952315) 4P/40kA,mod+contact
Valid Article
LIGHTNING-SURGE PROT. type2 (Dehn952315) 4P/40kA,mod+contact
Form
This SPD provides Type 2 protection for 230/400 V AC installations, using heavy-duty zinc oxide varistors and spark-gap technology for high discharge capability and coordinated Type 2 + Type 3 protection. It features plug-in protection modules, fault indication, and a floating changeover contact for remote signaling.
nominal voltage (UN): 230 / 400 V AC
maximum continuous operating voltage (Uc): 275 V AC (L–N), 255 V AC (N–PE)
voltage protection level (Up): ≤ 1.5 kV (L–N), ≤ 1.5 kV (N–PE)
short-circuit withstand capability (ISCCR): 50 kA
nominal discharge current (In): 20 kA (8/20 µs)
SPD type / class: type 2 / class II (IEC 61643-11)
Imax: 40 kA (8/20 µs)
Iimp (N–PE): 12 kA (10/350 µs)
number of poles: 3 + 1 (TT / TN-S)
dimensions: 90 x 72 x 66 mm
weight: 0.415 kg
Per piece.
Fit
installation location: main AC distribution board / sub-distribution
recommended back-up fuse / MCB: max. 125 A gG
AC system compatibility: 230/400 V AC (TT / TN-S, 3+1 configuration)
mounting type: 35 mm DIN rail
IP protection: IP20
max wire size: 1.5…35 mm² (stranded) / up to 25 mm² (flexible)
Function
The surge protective device (SPD) protects AC electrical installations and connected loads against transient overvoltages caused by lightning or switching operations.
Using heavy-duty varistors and spark-gap technology with “Thermo Dynamic Control” monitoring, it safely diverts surge energy to ground while maintaining coordinated Type 2 and Type 3 protection.
It provides reliable protection in L-N and N-PE modes and includes a floating changeover contact for remote signaling.