CHARGER-INVERTER (Victron Multiplus C) 12V/70A/1600W+cabling
Valid Article
CHARGER-INVERTER (Victron-Multiplus C) 12V/70A/1600W+cabling
Definition
The MultiPlus, as the name suggests, is a combined inverter and charger in one package. Its features include a true sine wave inverter, adaptive charging, hybrid PowerAssist technology, plus multiple system integration features.
Specifications
PowerControl: Yes
PowerAssist: Yes
Transfer switch (A): 16
INVERTER
Input voltage range (V DC) 9,5 – 17 V
Output Output voltage: 230 VAC ± 2% Frequency: 50 Hz ± 0,1% (1)
Cont. output power at 25°C (VA): (3) 1600
Cont. output power at 25°C (W): 1300
Cont. output power at 40°C (W): 1200
Cont. output power at 65°C (W): 800
Peak power (W): 3000
Maximum efficiency (%): 93 / 94
Zero load power (W): 8 / 10
Zero load power in AES mode (W): 5 / 8
Zero load power in Search mode (W): 2 / 3
CHARGER
AC Input Input voltage range: 187-265 VAC Input frequency: 45 – 65 Hz Power factor: 1
Charge voltage 'absorption' (V DC) : 14,4
Charge voltage 'float' (V DC) : 13,8
Storage mode (V DC) : 13,2
Charge current house battery (A)(4): 70 / 40
Charge current starter battery (A): 4 (12 V and 24 V models only)
Battery temperature sensor: yes
GENERAL
Auxiliary output (5): n. a.
Programmable relay (6) Yes
Protection (2): a - g
VE.Bus communication port: For parallel and three phase operation, remote monitoring and system integration
General purpose com. Port: n. a.
Remote on-off: Yes
Common Characteristics Operating temp. range: -40 to +65°C (fan assisted cooling) Humidity (non-condensing): max 95%
ENCLOSURE
Common Characteristics Material & Colour: aluminium (blue RAL 5012) Protection category: IP 21
Battery-connection battery cables of 1.5 meter
230 V AC-connection: G-ST18i connector Spring-clamp
STANDARDS
Safety EN-IEC 60335-1, EN-IEC 60335-2-29, IEC 62109-1
Emission, Immunity EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
Notes:
1) Can be adjusted to 60 HZ; 120 V 60 Hz on request
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 230 VAC on inverter output
g) input voltage ripple too high
3) Non-linear load, crest factor 3:1
4) At 25˚C ambient
5) Switches off when no external AC source available
6) Programmable relay that can a.o. be set for general alarm,
DC under voltage or genset start/stop function
AC rating: 230 V/4A
DC rating: 4 A up to 35 VDC, 1 A up to 60 VDC
Dimensions
Weight (kg): 10
Dimensions (hxwxd in mm): 375x214x110