(CHANGE-OVER SWITCH 2P/5kVA, VICTRON) TIMER RELAY, 250V/8A
NST
PELECOMMTS208
Valid Article
Account code:
61220
Last Updated on:
10/02/2026, 22:02:17
(CHANGE-OVER SWITCH 2P/5kVA, VICTRON) TIMER RELAY, 250V/8A
Form
Multifunction electronic time relay designed for control circuits requiring adjustable ON-delay and OFF-delay timing functions
Contact configuration: 1 changeover contact (SPDT, 1 CO)
- control supply voltage: 24–240 VAC / VDC
- supply frequency (AC): 48–63 Hz
- rated consumption: 4 VA (1.5 W)
- number of time ranges: 7
- time setting range: 50 ms to 100 h
- time adjustment: rotary selector and scale adjustment
- indication:
- green LED ON: supply voltage present
- green LED flashing: timing in progress
- yellow LED ON/OFF: relay output status
- output rated voltage: 250 VAC
- switching capacity: 2000 VA (8 A / 250 VAC)
- mechanical lifetime: 20 × 10⁶ operations
- electrical lifetime: 2 × 10⁵ operations at 1000 VA resistive load
- IP protection: IP40 (housing), IP20 (terminals)
- operating temperature: −25 °C to +55 °C
- storage temperature: −25 °C to +70 °C
- overvoltage category: III
- rated surge voltage: 4 kV
- duty cycle: 100 %
- module width: 17.5 mm
Per piece.
Fit
- supply connection: terminals A1 (+) and A2 (−) for AC or DC supply
- control input: terminal B1, not potential-free
- control wiring: switch connected between A1 and B1
- control input characteristics:
- automatic trigger level adaptation to supply voltage
- minimum control pulse: 50 ms (DC), 100 ms (AC)
- maximum control line length: 10 m
- output interface: 1 potential-free changeover contact
- output terminals: 15 (common), 16 (NC), 18 (NO)
- rated output current: 8 A
- recommended fuse protection: 8 A fast acting
- mounting interface: 35 mm DIN rail (EN 50022)
- mounting position: any
- terminal capacity:
- 0.5–2.5 mm² (single conductor)
- up to 4 mm² (solid conductor)
- 2 × 0.5–1.5 mm² (multi-conductor)
- terminal tightening torque: max. 1 Nm
Function
Primary function:
generation of adjustable ON-delay and OFF-delay timing for control circuits
Functional behavior and limitations:
ON-delay (E):
- timing starts when supply voltage is applied
- relay switches ON after the set time has elapsed
- interruption of supply resets the timing cycle
OFF-delay (R):
- supply voltage must be permanently applied
- timing starts when the control contact opens
- relay switches OFF after the set time has elapsed
- re-closing the control contact resets the timing
- designed for control and signaling circuits only
- not intended for direct switching of power loads
Typical applications:
- control panels and automation systems
- delayed start or stop of motors and actuators
- lighting and ventilation timing
- alarm and signaling delay functions