RELAY voltage monitoring (Finder 70.42) 380-415VAC, 8A

NST PELECOMMRF408

Valid Article



OC subscriptions: included in supply or field order tools (e.g. UniField)
SC subscriptions: included in supply or field tools
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)

https://unicat.msf.org/web/image/product.template/557896/image_1920?unique=dd6cf5c

This combination does not exist.

Add article to list

   

Add Kit To Wishlist

   

RELAY voltage monitoring (Finder 70.42) 380-415VAC, 8A

Form

Three-phase voltage monitoring relay designed to supervise voltage quality, phase conditions, and neutral integrity in three-phase electrical systems

  • nominal system voltage: 380–415 VAC
  • frequency: 50/60 Hz
  • monitoring voltage range: 300–480 VAC
  • monitoring functions: overvoltage, undervoltage, window mode, phase loss, phase rotation, voltage asymmetry, neutral loss
  • fault memory: selectable (with or without memory)
  • asymmetry threshold: adjustable 5–25 % of UN
  • rated insulation category: overvoltage category III
  • IP protection: IP20
  • operating temperature: −20 °C to +60 °C
  • standards compliance: IEC / EN 60255, IEC / EN 61810
  • module width: 35 mm

Per piece.

Fit

  • supply connection: three-phase voltage sensing via L1, L2, L3, with neutral connection required
  • output interface: 2 changeover relay contacts (DPDT, 2 CO)
  • rated output current: 8 A (control circuits)
  • peak switching current: 15 A
  • contact material: AgNi
  • output contact behavior:
    • contacts close when monitored voltage and phase parameters are within set limits
    • contacts open on undervoltage, overvoltage, phase loss, incorrect phase rotation, voltage asymmetry, or neutral loss
  • electrical integration: interface with contactor coils, alarms, interlocks, or control system inputs
  • mounting interface: 35 mm DIN rail
  • terminal type: screw terminals
  • installation environment: electrical panels and control cabinets
Image

Function

Primary function:

  • continuous monitoring of three-phase voltage quality, phase sequence, and neutral integrity

Functional behavior and limitations:

  • detects abnormal voltage conditions, phase-related faults, asymmetry, and neutral loss
  • supports fault memory operation requiring manual reset when enabled
  • provides automatic recovery when fault memory is disabled and conditions return within acceptable limits
  • intended for monitoring and control purposes only
  • not designed for direct power switching of loads

Typical applications:

  • motor protection via control circuits
  • pumps, compressors, and ventilation systems