CONTACTOR (Tesys) 220-240V, 16A, 1NO-1NC, 2P, modular
Valid Article
CONTACTOR (Tesys) 220-240V, 16A, 1NO-1NC, 2P, modular
Form
Modular contactor designed for remote switching of lighting, heating and small motor circuits
- rated operational current:
- 16 A (AC-7A)
- 5 A (AC-7B)
- contact configuration: 1 NO + 1 NC
- number of poles: 2P
- rated operational voltage (Ue): ≤ 250 VAC
- control circuit voltage (Uc): 220–240 VAC, 50 Hz
- rated insulation voltage (Ui): 500 V
- rated impulse withstand voltage (Uimp): 4 kV
- rated making and breaking capacity: 40 A at 400 VAC
- short-time withstand current (Icw):
128 A (10 s)
40 A (30 s)
- dimensions (HxWxD): 81 × 17.5 × 62.5 mm
- weight: 0.11 kg
Per piece.
Fit
Mounting on standard 35 mm DIN rail
Power terminals: screw clamp terminals
up to 6 mm² (single conductor)
up to 4 mm² (two conductors)
Control terminals: screw clamp terminals
up to 2.5 mm²
Associated fuse rating: 16 A gL (≤ 440 V)
Function
Electromechanical modular contactor designed for switching single-phase loads,
used for remote switching of lighting circuits, electric heating loads and small motor applications
operates with AC control voltage (220–240 VAC, 50 Hz)
provides galvanic isolation between control circuit and power circuit
suitable for frequent switching applications
limitations:
not suitable for heavy industrial motor starting beyond AC-7 rating
requires appropriate upstream short-circuit protection