LIGHTNING-SURGE PROT. type 1, 1P+E/10kA, fixed
Valid Article
LIGHTNING-SURGE PROT. type 1, 1P+E/10kA, fixed
Form
This SPD is designed to provide robust surge protection in low-voltage distribution systems, ensuring reliable limitation of high-energy transient overvoltages.
nominal system voltage (Un): 230 V AC
maximum continuous operating voltage (Uc): 350 V AC
voltage protection level (Up): 1.5 kV
short-circuit withstand (Isccr): coordination with gG 160 A fuse
nominal discharge current (In): 25 kA (10/350 µs)
response time: < 25 ns
Spd type / class: type 1 + 2 (IEC 61643-11)
imax: 50 kA
number of poles: 1P + N
dimensions: 81.4 × 36 × 71 mm
weight: 318.1 g
includes:
1 × SPD module
1 × instruction manual
Per piece.
Fit
installation location: main distribution board / sub-distribution
recommended back-up fuse / MCB: gG 160 A
Ac system compatibility (earthing): TN-S / TT / IT
mounting type: DIN rail
indoor use IP40 (in modular enclosure)
max wire size: 6 mm²
Function
The surge protective device (SPD) protects electrical systems and sensitive equipment from transient overvoltages caused by lightning strikes or switching events. It safely diverts surge energy to earth, limiting the voltage reaching downstream devices. The Type 1+2 design allows it to handle direct lightning impulses while also providing protection against switching transients.