LIGHTNING-SURGE PROT. type 1, 3P+E/10kA, fixed
Valid Article
LIGHTNING-SURGE PROT. type 1, 3P+E/10kA, fixed
Form
This SPD is designed for three-phase installations requiring robust Type 1+2 surge protection with both MOV and GDT technology and remote signalling.
nominal system voltage (Un): 230/400 V AC
maximum continuous operating voltage (Uc): 350 V AC (L/N), 255 V AC (N/PE)
voltage protection level (Up): < 1.5 kV (L/N and N/PE)
short-circuit withstand (Isccr): 25 kA
nominal discharge current (In): 25 kA (L/N and N/PE)
response time: < 25 ns
spd type / class: type 1 + 2 (IEC/EN 61643-11)
imax: 50 kA
number of poles: 3P + N
dimensions: 84 × 72 × 71 mm
weight: 590 g
Per piece.
Fit
installation location: main distribution board / small commercial / residential
recommended back-up fuse / MCB: gG 160 A or associated NG125 / C120 breakers (80 A C-curve)
ac system compatibility (earthing): TT / TN-S
mounting type: DIN rail (clip-on)
indoor or outdoor use: indoor — front face IP40, IK05 protection
max wire size: 10…35 mm² rigid / 10…25 mm² flexible (tunnel terminals)
Function
The Surge Protective Device (SPD) protects three-phase electrical systems from transient overvoltages generated by lightning strikes or switching events. It safely diverts surge energy to earth, limiting overvoltage reaching downstream equipment. The device integrates MOV + GDT technology for coordinated energy handling and includes remote signalling (1 C/O contact) for end-of-life indication.