LIGHTN-SURGE PROT t. 1+2 (ABB 2CTB815710R0700) 4P/80kA,mod
Valid Article
LIGHTN-SURGE PROT t. 1+2 (ABB 2CTB815710R0700) 4P/80kA,mod
Form
This SPD provides combined type 1 and type 2 protection for three-phase distribution systems, using pluggable cartridges and integrated thermal disconnection to ensure safe operation under high lightning currents.
nominal system voltage (Uc): 275 V AC
maximum continuous operating voltage (Uc d.c): —
voltage protection level (Up): 1.35 kV (L-PE), 1.2 kV (L-N), 1.1 kV (N-PE)
short-circuit withstand (Isccr): 25 kA
nominal discharge current (In): 12.5 kA (8/20 µs)
response time: < 25 ns
SPD type / class: type 1 + 2 (classes I–II)
Imax: 80 kA (8/20 µs)
Iimp: 12.5 kA (10/350 µs)
number of poles: 3P + N
dimensions: 95 × 71.2 × 69.4 mm
weight: 600 g
includes:
1 × SPD module
1 × instruction manual
Per piece.
Fit
installation location: main distribution board / sub-distribution
recommended back-up fuse / MCB: up to 160 A gG or 125 A MCB (curve B or C)
AC system compatibility: TT / TN-S
mounting type: 35 mm DIN rail
IP protection: IP20
max wire size: 2.5…35 mm² (solid), 2.5…25 mm² (stranded)
Function
This SPD handles high-energy surges generated by lightning (10/350 µs) as well as switching transients (8/20 µs). It provides protection in common and differential modes for three-phase + neutral networks. Thanks to QuickSafe technology and the integrated thermal disconnector, the SPD safely isolates itself during thermal overload or end-of-life events. Pluggable cartridges simplify maintenance while ensuring continuous protection performance.