UPS (Eaton 5P Gen2 650 RT1U Net pack) 650VA 230V
Valid Article
UPS (Eaton 5P Gen2 650 RT1U Net pack) 650VA 230V
Form
Compact 1U rackmount uninterruptible power supply designed for high-density IT and network environments, featuring an integrated network card for remote monitoring and management.
Physical format 1U rackmount enclosure (482.6 mm / 19-inch standard)
Display: graphical LCD display for status monitoring, configuration, and electrical measurements
Cooling: active cooling with internal fan
Acoustic noise < 35 dBA at 1 meter in line and AVR modes
Dimensions (W × D × H): 438 × 361 × 43.2 mm
Weight: 8.6 kg
Includes:
- 1 × UPS unit (Eaton 5P650IRNG2) with pre-installed network card
- 2 × IEC-IEC output cables (IEC C13)
- 1 × USB communication cable
- 1 × Rack mounting kit (rack ears)
- 1 × Quick start guide and safety instructions
Per piece.
Fit
Power capacity: 650 VA / 520 W
Input specifications:
- Voltage range: 160–294 V AC (adjustable down to 150–294 V)
- Frequency range:
- 47–70 Hz (50 Hz system)
- 56.5–70 Hz (60 Hz system)
- down to 40 Hz in low sensitivity mode
- Connection: 1 × IEC C14 inlet
Output specifications:
- Voltage: 230 V AC default (selectable 200 / 208 / 220 / 230 / 240 V)
- Frequency: 50 / 60 Hz (auto-sensing)
- Topology: line-interactive with automatic voltage regulation (AVR)
Connections and interfaces:
- Output sockets: 4 × IEC C13
- Communication interfaces:
- Integrated Ethernet network card
- USB (HID compliant)
- RS-232 serial port
- Dry contacts and Remote On/Off / Remote Power Off terminals
Battery system:
- Battery type: sealed lead-acid (VRLA), maintenance-free
- Battery rating: 6 V / 9 Ah
- Quantity: 2 batteries
- Battery management: ABM® advanced battery management
- Battery replacement: user-replaceable batteries with front access
Function
A Line Interactive UPS that uses Automatic Voltage Regulation (AVR) to correct voltage sags and surges (Buck/Boost) without draining the battery. Uniquely, this model comes with a Network Management Card pre-installed, making it "IoT-ready" for centralized supervision out of the box.
Specific Applications:
Wall-Mount Comms Cabinets: The 1U height and short depth (361 mm) are specifically adapted for shallow network racks found in field offices, allowing protection of VSAT modems and switches where space is strictly limited.
Remote Fleet Supervision: The integrated Network Card allows logisticians to remotely monitor critical parameters (battery health, load level, grid availability) from the capital or HQ, which is vital for managing equipment in unmanned or hard-to-access radio rooms.
Generator Tolerance: The configurable "Low Sensitivity Mode" widens the input frequency acceptance window (down to 40 Hz). This prevents the UPS from constantly cycling to battery power when running on small, unstable field generators, preserving battery life for actual outages.