LIGHTNING-SURGE PROT. type 1+2 (Citel, DS50PV-1500G/12KT1)

NST PELEPROTILDF

Valid Article



OC subscriptions: included in supply or field order tools (e.g. UniField)
SC subscriptions: included in supply or field tools
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)

https://msf.oodin.sh/web/image/product.template/587461/image_1920?unique=8545435

This combination does not exist.

Add article to list

   

Add Kit To Wishlist

   

LIGHTNING-SURGE PROT. type 1+2 (Citel, DS50PV-1500G/12KT1)

Form

This device provides combined lightning and surge protection for high-voltage photovoltaic strings, offering coordinated protection in both common and differential modes.

  • nominal system voltage (Uocstc): 1250 V DC

  • maximum continuous operating voltage (Ucpv): 1500 V DC

  • voltage protection level (Up): 5.3 kV (@ In, 8/20 µs, +/- and +/PE)

  • short-circuit withstand (Iscpv): 15 000 A

  • nominal discharge current (In): 15 kA (8/20 µs)

  • response time: not specified (MOV technology)

  • Spd type / class: type 1+2 (IEC 61643-31)

  • imax: 40 kA per pole (8/20 µs), 60 kA total

  • iimp: 6.25 kA per pole (10/350 µs), 12.5 kA total

  • number of poles: +/-/PE (3 terminals)

  • technology: MOV

  • dimensions: 90 × 54 × 67 mm

  • weight: 0.475 kg


Per piece.

Fit

  • installation location: Pv string combiner box / DC distribution enclosure

  • recommended back-up fuse / MCB: none required (internal thermal disconnector)

  • Dc system compatibility: PV +/-/Pe system (common and differential protection)

  • mounting type: 35 mm din rail

  • indoor use: Ip20 (inside enclosure)

  • max wire size: 2.5–25 mm² screw terminals







Function

This surge protection device safeguards photovoltaic installations from lightning currents and transient surges. It provides both common-mode and differential-mode protection for DC strings up to 1500 V. The internal thermal disconnector ensures safe end-of-life operation, while optional remote signaling allows monitoring of module status. Its MOV-based Type 1+2 design enables protection against both direct lightning effects and switching surges in PV systems.