LIGHTNING-SURGE PROT. type 2 (Citel, DS50VGPVS-600G/51)
Valid Article
LIGHTNING-SURGE PROT. type 2 (Citel, DS50VGPVS-600G/51)
Form
This SPD provides Type 2 protection for PV installations up to 720 V DC, using VG technology (high-energy varistor + gas tube) for long service life, zero leakage current, and reliable protection in common and differential modes.
nominal system voltage (Uocstc): 600 V DC
maximum continuous operating voltage (Ucpv): 720 V DC
voltage protection level (Up): 3.4 kV (+/–), 2.2 kV (+/PE or –/PE)
short-circuit withstand (IscpV): 1 000 A
nominal discharge current (In): 15 kA (8/20 µs)
SPD type / class: type 2 (IEC 61643-31)
Imax: 40 kA (8/20 µs)
number of poles: + / – / PE
dimensions: 90 x 54 x 80 mm
weight: not specified
Per piece.
Fit
installation location: PV string combiner / DC distribution enclosure
recommended back-up fuse / MCB: none required (internal thermal disconnector)
PV system compatibility: + / – / PE configuration (common and differential protection)
mounting type: 35 mm DIN rail
IP protection: IP20
max wire size: 2.5…25 mm² (screw terminals)
Function
The surge protective device (SPD) protects photovoltaic systems and connected equipment from transient overvoltages caused by lightning or switching operations.
Using VG technology (varistor + gas tube), it diverts surge energy to ground while maintaining zero leakage current and ensuring reliable Type 2 protection.
It provides common-mode and differential-mode protection for PV arrays and downstream equipment.