LIGHTNING-SURGE PROT. type 2 (Citel, DS50VGPVS-1000G/51)

NST PELEPROTIL2T

Valid Article



OC subscriptions: included in supply or field order tools (e.g. UniField)
SC subscriptions: included in supply or field tools
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)

https://msf.oodin.sh/web/image/product.template/587466/image_1920?unique=910b9a7

This combination does not exist.

Add article to list

   

Add Kit To Wishlist

   

LIGHTNING-SURGE PROT. type 2 (Citel, DS50VGPVS-1000G/51)

Form

This SPD provides Type 2 protection for PV installations up to 1200 V DC, using VG technology (high-energy varistor + gas tube) for long service life, zero leakage current, and strong protection in common and differential modes.

  • nominal system voltage (Uocstc): 1000 V DC

  • maximum continuous operating voltage (Ucpv): 1200 V DC

  • voltage protection level (Up): 5.1 kV (+/–), 2.8 kV (+/PE or –/PE)

  • short-circuit withstand (IscpV): 15 000 A

  • nominal discharge current (In): 15 kA (8/20 µs)

  • SPD type / class: type 2 (IEC 61643-31)

  • Imax: 40 kA per pole (8/20 µs)

  • number of poles: + / – / PE

  • dimensions: 90 x 54 x 80 mm

  • weight: 0.306 kg

Per piece.

Fit

  • installation location: PV string combiner / DC distribution enclosure

  • recommended back-up fuse / MCB: none required (internal thermal disconnector)

  • PV system compatibility: + / – / PE configuration (common and differential protection)

  • mounting type: 35 mm DIN rail

  • IP protection: IP20

  • max wire size: 2.5…25 mm² (screw terminals)




Function

The surge protective device (SPD) protects photovoltaic systems and connected equipment from transient overvoltages caused by lightning or switching events.
Using VG technology (varistor + gas tube), it safely diverts surge energy to ground while maintaining zero leakage current and ensuring long service life.
It provides effective common-mode and differential-mode protection for PV arrays and downstream equipment.