MULTIFUNCTION MEASURING UNIT (Schneider PM5110) Modbus

NST PELEMEASFR1-

Valid Article



OC subscriptions: included in supply or field order tools (e.g. UniField)
SC subscriptions: included in supply or field tools
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)

https://msf.oodin.sh/web/image/product.template/588119/image_1920?unique=9fce31f

This combination does not exist.

Add article to list

   

Add Kit To Wishlist

   

MULTIFUNCTION MEASURING UNIT (Schneider PM5110) Modbus

Form

Compact power meter for power monitoring and quality analysis in single- and three-phase networks. Designed for flush mounting with a monochrome graphic LCD and Modbus RTU communication.

  • shape: flush-mounted rectangular instrument with front display and push buttons

  • material: insulated enclosure with screw-terminal connections

  • quality requirements: indoor use up to 2000 m altitude, operating −25 to 70 °C depending on performance, pollution degree 2

Electrical characteristics

  • measurement functions: voltage, current, frequency, active/reactive/apparent power, active/reactive energy, power factor, harmonics up to the 15th order

  • sampling: 64 samples per cycle

  • voltage measurement range: phase-to-phase up to 1000 V AC, phase-to-neutral 20…440 V AC

  • current measurement (via CT inputs): 50…8500 mA

  • accuracy: active energy class 0.5S, typical ±0.5% for active/reactive/apparent power

  • communication: Modbus RTU over RS-485, 2-wire isolated

  • power supply: 90…450 V AC or 100…300 V DC

  • inputs / outputs: screw terminals for voltage, CTs and RS-485, 1 digital output

  • dimensions: 96 × 96 × 72–92 mm

  • weight: approx. 380 g

Includes

  • 1 × main unit

Per piece.

Fit

  • installation method: flush-mount installation using standard 96 × 96 mm panel cut-out, wiring of voltage and CT terminals

  • electrical compatibility: suitable for single-phase and three-phase networks, rated CAT III 600 V

  • communication compatibility: Modbus RTU over RS-485 for integration into energy management and automation systems



Function

  • measure RMS voltage and current, frequency, active/reactive/apparent power, energy and power factor

  • record instantaneous, minimum and maximum values for analysis

  • perform basic power quality diagnostics including harmonic measurement up to the 15th order

  • communicate measurements and alarms to external monitoring systems via Modbus RTU