REFRIGERANT GAZ RECOVERY CYLINDER, 21.6L, for A2L gases

NST CCLITOOLGR12

Valid Article


Hazardous materials and products (identified by their 4-digit transport UN-number) must be transported under certain conditions as specified in the MSDS sheet (Material Safety Data Sheet).

OC subscriptions: included in supply or field order tools (e.g. UniField)
SC subscriptions: included in supply or field tools
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)

https://msf.oodin.sh/web/image/product.template/589361/image_1920?unique=234d563

This combination does not exist.

Add article to list

   

Add Kit To Wishlist

   

REFRIGERANT GAZ RECOVERY CYLINDER, 21.6L, for A2L gases

Form

A 21.5L, double valve recovery cylinder.

Specifications:

  • service pressure: 27 bar
  • air tightness pressure: 27 bar
  • bursting volumetric expansion rate: >20%
  • nominal water capacity: 21.5 l
  • tank test pressure: 55 bar
  • bursting pressure: >108 bar
  • body material: HP325 or HP345
  • tare weight: 12,7 kg
  • size (w x h): 300 mm x 480 mm

Fit

Connection: 1/4″ FL-M (7/16-20).

This 21.5 l cylinder can store a maximum of 18kg of R32.

It must be used to store only 1 type of gas. Never fill it with a mix of different gases.

Function

The cylinder is used for safe recovery, storing and/or transporting refrigerant gas recovered from a refrigeration/HVAC system.

  • This is an A2L gas cylinder. It can only be used for A2L gases, such as R-32
  • This refrigerant gas cylinder must not be used with A3 gases such as R290 or R600A
  • It should not be used for A1 gases such as R410A, R134a, and R22. There is a specific refrigerant gas recovery cylinder for A1 gases