ASSEMBLY, CHLORINATOR + GATE VALVE + SET COUPLINGS 2"

STD CWATASSYD03

Valid Article

Former Code(s): CWATACHL01- CWATASSY01-11
OC subscriptions: included in supply or field order tools (e.g. UniField)
SC subscriptions: included in supply or field tools
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)

This combination does not exist.

See Related

Add article to list

   

Add Kit To Wishlist

   

ASSEMBLY, CHLORINATOR + GATE VALVE + SET COUPLINGS 2"

Form

Assembly made of a chlorinator, a 2" gate valve and two 2" half symmetrical Guillemin couplings.

Open article. Per assembled piece.

Fit

To be connected to a 2" flat hose coming from the control panel and a 2" hose going to the tank of the water treatment unit.

Part of kits:

  • KWATKTRE10- - KIT, WATER TREATMENT UNIT, 10 m³/h
  • KWATMTRE14- - (water treatment unit) MODULE DISINFECTION, box nº4

Function

Put the chlorinator as close as possible to the potable water reservoir and connect it to the 2" flat hose coming from the control panel and a 2" hose going to the tank.

  • Make sure that the water will be flowing in the direction indicated by the arrow on the chlorinator.
  • Make sure that the water level in the reservoir isn't a lot higher than inside the chlorinator, otherwise it won't work.
  • It is best to fill the chlorinator completely with water after the chlorine tablets have been added (see later) to obtain the best results from the start.