(generator) CTI AUTOMATIC TRANSFER SWITCH, 3 phase, 125A

NSL PELESWIT3H2-

Valid Article

OC subscriptions: included in supply or field order tools (e.g. UniField)
SC subscriptions: included in supply or field tools
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)
https://unicat.msf.org/web/image/product.template/563450/image_1920?unique=c4a333f

This combination does not exist.

Documents See Related

Add article to list

   

Add Kit To Wishlist

   

(generator) CTI AUTOMATIC TRANSFER SWITCH, 3 phase, 125A

Definition

Benefits
• Fully automatic mains failure sensing and generator set start signal
• Pre-programmed enabling the panel to run on installation with the ability to customise if necessary
• Fast acting switches reduce transfer times between set and utility power
• Integration with FG Wilson digital control panels

Features
• Automatic and manual operation
• Automatically provides generator set start signal upon detection of mains failure, overvoltage or loss of phase
• Automatic mains re-transfer function
• Flexible, upgradeable options
• Test operations and sequences accessible from panel or remotely
• Manual switch operation possible via external handle
• LED functions display showing generator set / mains availability and switch position
• LCD display for voltage and timers
• Load transfer panel range meets ATS IEC 60947-6-1 standard

Specifications

Given for the 125 A 50Hz model

Frequencies: 50 Hz
Thermal current Ithe 40 °C (A): 125
Thermal current Ithe 50°C (A): 110
Thermal current Ithe 60°C (A): 100
Assigned insulation voltage Ui (V) (power circuit): 600
Assigned impulse voltage Uimp (kV) (power circuit): 6
Assigned insulation voltage Ui (V) (auxiliary circuit): 300
Assigned impulse voltage Uimp (kV) (auxiliary circuit): 2.5

Other characteristic at 40°C

Rated operational currents Ie (A)

IEC 60947-3 characteristics 415 Vac

AC 21A / 21 B: 125/125
AC 22A / 22 B: 125/125
AC 23A / 23 B: 125/125

IEC 60947-6-1 characteristics 415 Vac

AC 31B: 125
AC 32B: 125

Operating class

Material class (according to 60947-6-1): PC

Maximum short circuit current using gG DIN fuse

Max short circuit (kA eff): 50
Associated fuse size (gG): 125
Peak current value: withstand and closing operation (kA peak): 13.5

Short circuit operation

Rated short time withstand current (kA eff) / 30 ms: 10

Transfer time

I-O / O-I / II-O / O-II (ms): 50
I-II or II-I (ms): 180
Blackout time during comutation under Un (ms): 120

Power input

Peak current during operation (A): 20
Continuous power consumption (VA): 6

Mechanical characteristics

Number of mechanical operations (according to 60947-6-3): 10000

Cables connection

Minimum cable size (Cu mm2): 50
Maximum cable size (Cu mm2): 70

Dimensions

Height (mm): 600
Width (mm): 400
Depth (mm): 200
Weight (kg): from 20 to 25 (including accessories)

Instructions for use

Consult manual for detailed installation instructions.

Image

Precautions for Use

To be installed only by qualified persons!