LIGHTNING-SURGE PROTECTION type 1+2, 2P, high energy, mod.
Discontinued Article
LIGHTNING-SURGE PROTECTION type 1+2, 2P, high energy, mod.
Form
This device provides combined Type 1 and Type 2 protection for photovoltaic generator circuits, with an integrated SCI short-circuiting and isolation system to prevent DC arc-flash and fire hazards.
nominal system voltage (Ucpv): ≤ 1000 V DC (DC+ → DC−)
maximum continuous operating voltage (Ucpv to PE): ≤ 725 V DC
voltage protection level (Up): 2.5 kV (DC+/DC− → PE), 4.75 kV (DC+ → DC−)
short-circuit withstand (Iscpv): 1000 A
nominal discharge current (In): 15 kA (8/20 µs)
response time: ≤ 25 ns
Spd type / class: type 1 + type 2 (EN 50539-11)
Imax / total discharge current: 30 kA (8/20 µs total)
Iimp: 6.25 kA per pole (10/350 µs)
IP20
dimensions: 90 × 72 × 69 mm
weight: 433 g
Per piece.
Fit
installation location: photovoltaic generator combiner / dc distribution enclosure
recommended back-up fuse / mcb: not required (integrated sci disconnector)
Dc system compatibility: PV dc+ / dc− / Pe configuration
mounting type: 35 mm din rail (EN 60715)
indoor use: Ip20
max wire size: 1.5 mm² (min) to 35 mm² stranded / 25 mm² flexible
Function
This surge protective device provides combined lightning current and surge protection for photovoltaic systems up to 1000 V DC. Its SCI (Short-Circuit and Isolation) technology ensures safe disconnection of DC arcs, preventing fire hazards. The device protects both differential and common modes, offering high-energy capability and fast response, suitable for PV generator circuits exposed to lightning surges and switching disturbances.