LIGHTNING-SURGE PROT. type 1+2 (A9L16482) 3P+E/10kA, modular
Valid Article
LIGHTNING-SURGE PROT. type 1+2 (A9L16482) 3P+E/10kA, modular
Form
This SPD provides coordinated type 1 and type 2 protection for three-phase low-voltage distribution systems, using MOV and GDT technology to handle both lightning impulses and switching surges.
nominal system voltage (Ue): 230/400 V AC (+/–10 %)
maximum continuous operating voltage (Uc): 350 V AC (L/N), 255 V AC (N/PE)
voltage protection level (Up): < 1.5 kV (type 1+2)
short-circuit withstand (Isccr): 50 kA
nominal discharge current (In): 20 kA (8/20 µs)
response time: < 25 ns
SPD type / class: type 1 + 2
Imax: 50 kA
Iimp: 12.5 kA (L/N), 50 kA (N/PE)
number of poles: 3P + N
dimensions: 89 × 72 × 69 mm
weight: 619 g
includes:
1 × SPD module
1 × instruction manual
Per piece.
Fit
installation location: main distribution board / sub-distribution
recommended back-up fuse / MCB: gG 160 A or NSX160E 80 A (25 kA)
AC system compatibility: TT / TN-S
mounting type: 35 mm DIN rail
IP protection: IP40 (front face)
max wire size: 10…35 mm² (phase), 16…35 mm² (earth)
Function
This SPD protects three-phase electrical installations from transient overvoltages caused by lightning or switching operations. Its MOV + GDT hybrid protection provides a strong capability to handle high-energy surge currents in both common and differential modes. Mechanical indication and remote signalling (1 C/O contact) allow immediate monitoring of device status and end-of-life condition.