Form

Battery charger AC to DC and DC to DC operation.

  • input 12 volts DC and/or 230 Volts AC, charging current 80 ampere
  • charge voltage absorption (V DC) 14.3 / 28.5
  • charge voltage float (V DC) 13.5 / 27.0
  • H x W x D: 500 x 255 x 30 mm
  • AC connection 4 mm²
  • operating temperature range: -20 to +60°C (fan assisted cooling
  • humidity (non condensing): max 95%
  • dry location only
  • weight 12 kg

Closed article: Victron centaur 12/80. Per piece.

Fit

Fit with batteries and Victron accessories.

Function

Three-stage charging, with temperature compensation.
The system charges at bulk rate until the output has reduced to 70% of the rated Amps, at which a 4 hour timer begins.
After the timed period the charger switches to float rate.
An internal temperature sensor is used to compensate the charge voltage with – 2 mV/ºC (– 1 mV/ºF) per cell.
A DIP switch is available to select the optimum charge/float voltages for flooded lead-acid, gel or AGM batteries.