SHUNT release (Schneider GV2ME) 230V

NSL PELECOMMCSS

Valid Article

OC subscriptions: included in supply or field order tools (e.g. UniField)
SC subscriptions: included in supply or field tools
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)
https://unicat.msf.org/web/image/product.template/558466/image_1920?unique=805fa66

This combination does not exist.

Add article to list

   

Add Kit To Wishlist

   

SHUNT release (Schneider GV2ME) 230V

Form

Schneider Electric component GVAX225: TeSys GV2 - safety undervoltage trip - 220...240 V AC 50 Hz.

Main characteristics:

  • Range: TeSys
  • Device short name: GVAX
  • Product or component type: Safety undervoltage trip
  • Product compatibility: GV2ME

Additional features:

  • Control circuit voltage 220...240 V AC 50 Hz
  • Control circuit voltage limits 0.85...1.1 Un
  • [Ui] rated insulation voltage 600 V AC UL 508
  • 690 V AC IEC 60947-1
  • 600 V AC CSA C22.2 No 14
  • Threshold tripping voltage 0.7...0.35 Un
  • Inrush power in VA 12 VA AC
  • Inrush power in W 8 W DC
  • Hold-in power consumption in VA 3.5 VA AC
  • Hold-in power consumption in W 1.1 W DC
  • Operating time 10...15 ms IEC 60947-1
  • On-load factor 100 %
  • Connections:
    Terminals Screw clamp terminals 1 0.75...2.5 mm² flexible without / Screw clamp terminals 1 1...2.5 mm² solid / Screw clamp terminals 2 0.75...2.5 mm² flexible without / Screw clamp terminals 2 1...2.5 mm² solid / Screw clamp terminals 1 0.75...1.5 mm² flexible with / Screw clamp terminals 2 0.75...1.5 mm² flexible with
  • Tightening torque: <= 1.4 N.m screw clamp terminals
  • Mechanical durability: 10000 cycles with GV3P and GV3L / 30000 cycles with GV2ME and GV2P
  • Quantity per set: 10
  • Product weight 0.105 kg

Fit

GVAX225 used only with motor starter and protector TeSys GV2ME. For use with GV2ME GVAX Series.

Function

Disconnects starter unit when there is a reduced applied voltage or supply failure.
Prevents automatic restarting after mains supply failure.