CHARGER-INVERTER (Combi sinus) 1400W 45A

NSL PELECHIN4C214

Valid Article

OC subscriptions: included in supply or field order tools (e.g. UniField)
SC subscriptions: included in supply or field tools
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)

This combination does not exist.

Add article to list

   

Add Kit To Wishlist

   

CHARGER-INVERTER, 45A + solar option

Definition

Battery charger and inverter combined in one single device, automatic, with constant output power.

Synonym

combi

Specifications

  • Overcharge protection
  • Input voltage:
    • 9.5 - 16 V DC
    • 150 - 265 V AC
  • Output power: 1100 W
  • Peak output power: 1400 W for 30 minutes maximum
  • Consumption on standby: 4 W
  • Modified sine waves
  • Switch-over time (from inverter to charger and vice versa) < 20 microseconds
  • Integrated 30 A solar panel controller (max. 150 W)
  • Temperature sensor
  • No interference with radio installations

Instructions for use

Suitable for radio installations.

Calculate the power and do not overload the device.

The temperature sensor reduces the charging voltage when the battery temperature increases. It is therefore essential to connect this sensor in order to protect your batteries against premature ageing or destruction due to gel desiccation.

This charger/inverter is equipped with an internal voltage limiter that will disconnect the AC power input automatically when the voltage exceeds 260 V. Many devices could be damaged by such a voltage. It is therefore essential to install an external voltage limiter (with a 245 V cutoff) on the input side to protect the devices connected to the charger/inverter (see "Related Articles" below).

If the input voltage is too low or too fluctuating, you are recommended to install a voltage regulator/stabilizer (see "Related Articles" below).

Check the polarity!

Always connect the RED cable to the "+" terminal and the BLACK cable to the "-" terminal.

Note

To order only an inverter, please contact your technical department.

Some restricted information has been hidden. Sign in to see this information

MSF requirements

Temperature sensor.

No interference with radio installations.