BREAKER RCBO, 630A 0.03-3A adjustable 36kA, 4P mould.

NSL PELERBO04A6C3

Discontinued Article

Former Code(s): PELEMCBO4A6C3
OC subscriptions: included in supply or field order tools (e.g. UniField)
SC subscriptions: included in supply or field tools
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)

This combination does not exist.

Add article to list

   

Add Kit To Wishlist

   

BREAKER RCBO, 630A, 0.03-3A adjustable, 36kA, 4P mould.

Form

Moulded case Circuit Breaker MCCB with electronic earth leakage module, 4 pole, 630 Amps, 220 - 690 Volts, 50 - 60 Hz, Interrupting capacity 36 kA at 400 Volts. Equipped with earth leakage module with LCD screen, Adjustable sensitivity: 0.03 - 0.3 - 1 - 3 Amps, Adjustable tripping: 0 - 0.3 - 1 - 3 seconds, cable sizes, Flex Cu 185 mm² or 240 mm² rigid cable.

Per piece.

Fit

Fits with compatible Legrand DPX³-AB distribution boards and panels.

Options:

Residual current protection, without or integrated.
Legrand Power Control Station software.

Function

Adjustable circuit breaker, used to provide protection to electrical circuits and equipment.

Consult: section 6.5 Circuit Breakers, MSF – ICRC Electrical Installations and Equipment in the Field : Rules and Tools. Ver 0.

Please consult your OC's electrical referent for correct application and use.