MODULE UPS double convers. (Delta Amplon RT) 10kVA, 3ph/1ph
NST
KPROMPOSUC10A
Valid Article
HS Code:
854420
Last Updated on:
11/12/2024, 19:39:52
Hazardous materials and products (identified by their 4-digit transport UN-number) must be transported under certain conditions as specified in the MSDS sheet (Material Safety Data Sheet).
MODULE UPS double convers. (Delta Amplon RT) 10kVA, 3ph/1ph
Form
- Nominal power: 10 kVA/10 kW
- Nominal input voltage: 400/230 V AC
- Input voltage range:
- 305 - 485 V AC 100% load
- 138 - 305 V AC 40% - 100% load
- Input and output frequency: 50 or 60 Hz
- Power factor: >0.99
- Efficiency (full load): >92%
- Without battery
- 3-phase input
- 1-phase output
- With LCD-display
- Capacity: 10 kVA output
- Dimensions: WxDxH: 440 x 649 x 88 mm
- Weight: 16.6kg
There is no connection between the incoming power and the outgoing power. All possible electrical problems such as voltage spikes are eliminated.
This kit contains 3 articles:
- PELEUPSDC1DE - The electronic unit of the Delta 10 kVA extended model 3ph/1ph
- PELEUPSD06DXB - Battery cabinet with batteries with a total capacity of 20x9Ah
- PELEUPSD06DXP - Pack of spare filters (10 left, 10 right) and strips (40) for both the electronic unit and the battery cabinet
Fit
Can be used in any electrical installation. The UPS electronic unit always needs to be connected to at least one battery pack. Several battery packs can be installed in parallel to increase the backup time.
Function
An electronic unit, or also called a double conversion uninterruptible power supply (UPS), guarantees a perfect AC supply and is especially suitable for vulnerable and/or expensive equipment such as medical and laboratory equipment.