(Delta Amplon RT10kVA 3ph/3ph) ELECTRONIC UNIT

NST PELEUPSDB1DE

Valid Article

OC subscriptions: included in supply or field order tools (e.g. UniField)
SC subscriptions: included in supply or field tools
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)

This combination does not exist.

Add article to list

   

Add Kit To Wishlist

   

(UPS Delta Amplon RT10kVA 3ph/3ph) ELECTRONIC UNIT

Form

  • Input voltage range 100 - 300 V (note that between 100 V and 180 V input voltage, the output power is reduced by 50 - 100%; full power is available only at 180V AC and above). At higher (>300 V) or lower (<100 V) voltages the UPS switches to battery power
  • Input and output frequency 50 or 60 Hz
  • Power factor >0.99
  • Efficiency (full load) >92%
  • Without battery
  • With a LCD-display
  • Capacity 10kVA
  • 3 phase input
  • 1 phase output
  • With a LCD-display
  • Dimensions WxDxH: 440 X 649 X 88.2 mm
  • Weight: 16.6 kg

This item is the power supply ONLY.

When working on ONLINE mode there is no connection between the incoming power and the outgoing power. All possible electrical problems such as voltage spikes are eliminated.

To function in the case of a power-cut it needs a battery pack, which has to be ordered separately.

Closed article: DELTA RT-10K3P. Per piece.

Fit

To be used in anyelectrical installation always with a Delta RT battery cabinet.

    Function

    A double conversion uninterruptiblepowersupply (UPS) guarantees a perfect AC supplyand is especiallysuitable for vulnerableand/or expensiveequipmentsuch as medical and laboratory equipment.