GENERATOR (FG Wilson P400) 350kVA 400V 50Hz 3ph, diesel

NST PELEGENEF4H05

Valid Article

Hazardous materials and products (identified by their 4-digit transport UN-number) must be transported under certain conditions as specified in the MSDS sheet (Material Safety Data Sheet).
OC subscriptions: included in supply or field order tools (e.g. UniField)
SC subscriptions: included in supply or field tools
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)

This combination does not exist.

Documents See Related

Add article to list

   

Add Kit To Wishlist

   

GENERATOR (FG Wilson P400) 350kVA 400V 50Hz 3ph, diesel

Definition

The FG Wilson P400 is powered by the Perkins 2206A-E13TAG2 6 cylinder turbo charged water cooled 1500rpm diesel engine. It uses a 50Hz AVR alternator, all housed in a quiet, durable and weather resistant acoustic enclosure.

Controlled by a control panel, FG100, with a start/stop button and a single menu layout for ease of navigation, but can also come with an alternative control panel.

Comes with a bunded long range fuel tank, a water heater, a battery charger and 2 wire auto start/stop.

The generator is ready for parallel operation synchronous with other generators.

Specifications

  • output ratings prime/standby: 350/400 kVA at 400/230 V, 50 Hz
  • engine: Perkins 2206A-E13TAG2
  • alternator: FG Wilson FG29A280 or equivalent
  • control Panel: FG100 or alternative
  • fuel tank Capacity: 888 litres
  • fuel consumption at 100% load: prime/standby: 68.6/77.8 litres
  • noise level: 70 dB(A) at 7 m
  • running time: ~17 hours at 75% load
  • hard wired output only, no socket
Image
Some restricted information has been hidden. Sign in to see this information

Technical specifications

Engine:

  • 6 cylinder, 4 stroke, in line diesel engine
  • speed: 1500 rpm (for 50 Hz)
  • gross engine power: prime/standby: 324/368 kW
  • turbocharged, water cooled with electronic regulation
  • lubrication: engine oil, 40 liters, CH4 SAE15W-40

Alternator:

  • output: 400/230 V, 50 Hz, 3-Phase
  • power rating: prime/standby: 350/400 kVA, 280/320 kW
  • Excitation System: SHUNT
  • AVR model: A106 MKII or alternative

*Genset can be equipped with alternative alternators - to be specified at order

Dimensions

LxWxH: 3800 x 1131 x 2156 mm

Weight: 3161 kg

Transport Dangerous Goods

Generators might be considered as dangerous goods for transport:

  • If a shipper or supplier provides written or electronic documentation stating that a flushing and purging procedure for flammable liquid powered engines has been followed in compliance with Special Provision A70 the generator is not subject to IATA DGR regulations
  • If not complying with Special Provision A70 then the generator must be managed in compliance to IATA DGR regulations

Instructions for use

Do not fill the fuel tank while the engine is running.

For maximum safety and earthing, refer to the MSF guidelines on energy.

The P400 is equipped with electronical governor and electronic AVR. With this configuration it is prepared to operate in a set of parallel, synchronised generators.

For more details and power calculations refer to your technical department.

Maintenance

Usual maintenance interval is every 250 hours for this type of generator. For certain countries/locations a different maintenance interval might be applicable, check this with technical department.

Use the logbook generator 1500 rpm , article code: L041MECM19E-P.