(Fronius) ELECTRICITY METER (Fronius Smart Meter TS 65A-3)

NST PELESOLANF6EM

Valid Article

SC subscriptions: included in supply or field tools
OC subscriptions: included in supply or field order tools (e.g. UniField)
OC validations: approved for procurement and use by an OC for international or local orders specifying context and activity in Medical Standard Lists (MSL)
https://unicat.msf.org/web/image/product.template/587354/image_1920?unique=dd8c920

This combination does not exist.

See Related

Add article to list

   

Add Kit To Wishlist

   

(Fronius) ELECTRICITY METER (Fronius Smart Meter TS 65A-3)

Form

A bidirectional electricity meter measuring energy flows that come from the grid or flow into the grid. In conjunction with an inverter, a datamanager and a data interface, the electricity meter provides a clear overview of a user's own power consumption.

Technical specifications:

  • Nominal voltage: 208 - 400 V
  • Operating voltage range: -20 to +20 %
  • Nominal frequency: 45 - 65 Hz
  • Maximum current: 3 x 65 A
  • Grid type: 2PN, 3P, 3PN
  • Power line cross section: 1 - 16 mm²
  • Neutral line cross section: 1 - 16 mm²
  • CT's & Communication line cross section: 0.05 - 1.5 mm²
  • Power consumption: <=1 W
  • Starting current: 20 mA
  • Accuracy class: 1
  • Active energy accuracy: Class 1 (EN 62053-21) / Class B (EN 50470-3)
  • Reactive energy accuracy: Class 2 (EN 62053-23)
  • Short-time overcurrent : 1.950 A / 10 ms
  • Housing: 3 modules DIN 43880
  • Degree of protection: IP 51 (front frame), IP 20 (terminals)
  • Ambient temperature range: -25 to +65 °C
  • Dimensions (height x width x depth): 91.5 x 53.8 x 63.0 mm
  • Weight: 240 g
  • Interface to inverter: Modbus RTU (RS485)
  • Display: 3 x 8 digit / Touchscreen

Per piece.

Image

Fit

Mounting: Indoors (DIN rail).

The electricity meter can be mounted on a 35 mm DIN rail. The housing comprises 3 modules according to DIN 43880.

Image

Function

Used to visualize, control, and optimize energy flows for photovoltaic system. Used to manage energy consumptions.